Device Used
- INVERTER : IGBT (Semikron Make) Control PWM Technology With Pure Sine Wave Output
- RECTIFIER : Full Wave Rectifier By Using IGBT Charger Power Factor Correction
- FILTER : DC Power Capacitors with Choke Input Filter
Our Specialization
- Server Based Voltage Stabilizer
- Uninterrupted Power Supply
- Isolation Transformers
- Solor Energy based Products
Note: Image shown are just indicative and will change due to research and development activities.
| Parameter | Specification |
| Input Voltage | 295V-465V |
| Input Frequency | 50Hz +/-6% |
| DC Bus | 120, 180, 192, 240 & 360V DC |
| Rectifier | Bridge Rectifier FULL WAVE |
| Charger | PFC IGBT CHARGER |
| Input PF | >.97 |
| Charging Current | As per Battery Capacity |
| Charging Voltage | As per Battery Capacity |
| Ripple without battery | <1% |
| UPS Output Voltage | 230V AC +-1% @ Single Phase |
| Regulation | +/- 1% |
| Frequency | 50Hz +/- 0.1Hz. |
| Waveform | True Sine Wave |
| Total Harmonic Distortion | <2% Minimum for Linear Load, 5% for Non Linear Load |
| Overload Capacity | 125% for 10Mins, 150% for 1Sec. |
| Inverter Type | IGBT Based PWM With Instantaneous Sine Wave Control. |
| Duty Cycle | Continuous |
| Manual Bypass | Provided |
| Inverter Efficiency | > 93% |
| Converter Efficiency | > 94% |
| Converter Protection | MCB,and HRC Fuses, Soft Start for 0-60 seconds from input power |
| Inverter Production | MCB and HRC Fuses, High speed pulse by pulse electronic over voltage / under voltage production, Over current trip with reset |
| LCD Display | Output Voltage, DC Voltage,Load in Watts,Battery Low, Output Low/High, Overload. |