Device Used
- INVERTER :
IGBT (Semikron Make) Control PWM
Technology With Pure
Sine Wave Output - RECTIFIER :
Full Wave Rectifier By Using IGBT Charger
Power Factor Correction - FILTER :
DC Power Capacitors with Choke Input Filter
Note:
Image shown are just indicative and will change due to research and
development activities
Parameter | Specification |
Input Voltage | 170V-270V |
Input Frequency | 50Hz +/-6% |
DC Bus | 24V-192V DC |
Rectifier | Bridge Rectifier FULL WAVE |
Charger | IGBT Power Factor Charger |
Input PF | >.97 |
Charging Current | Depending upon the system |
Charging Voltage | Depending upon the system |
Ripple without battery | <1% |
UPS Output Voltage | 220V AC +-1% @ Single Phase |
Regulation | +/- 1% |
Frequency | 50Hz +/- 0.1Hz |
Waveform | True Sine Wave |
Total Harmonic Distortion | <2% Minimum for Linear Load, 5% for Non Linear Load |
Overload Capacity | 125% for 10Mins, 150% for 1Sec. |
Inverter Type | IGBT Based PWM With Instantaneous Sine Wave Control. |
Duty Cycle | Continuous |
Manual Bypass | Provided |
Inverter Efficiency | > 93% |
Converter Efficiency | > 94% |
Converter Protection | MCB,and HRC Fuses, Soft Start for 0-60 seconds from input power |
Inverter Production | MCB and HRC Fuses, High speed pulse by pulse electronic over voltage / under voltage production, Over current trip with reset |
LCD Display | Output Voltage, DC Voltage,Load in Watts,Battery Low, Output Low/High, Overload. |